Deflagration Door
A fusion explosion exhaust system that detects the gas generation caused by unexpected phenomena during the operation of BESS
and opens the doors to release gases, while instantly opening to release pressure in the event of sudden pressure increase or explosion, like a deflagration panel



Rapid opening to minimize damage from expansion gas and immediate operation at low pressure
Leak-proof and shatter-free design
Easy replacement and low maintenance costs
Product quantity and installation location can be selected based on the container size and the type of contents
| Set. Press. | 0.05~0.1 barg | Weight | - |
|---|---|---|---|
| Size | 500 X 500 mm | IP Level | IP 55 |
| Material | Aluminum + Stainless steel | IK Level | KS C IEC 62262 : 2002, IK10 |
| Fastener | M10 | Corrosion | KS C IEC 60068-2-52:2017 Test Criteria 1, No Corrosion |
| Vent Area | 0.25m² | Vibration | ASTM D4169, Truck test - High level for 3H |
| Fluid | Mixed Gas | ||
| Temperature | -20 ~ 80℃ | Certificate | (Linear actuator : UL94-V0) |
| Remark |
Active Venting System: NFPA 68 + NFPA 69 ㆍIn the event that off-gas is detected inside the ESS, the system opens the door to vent the gas safely to the outside. ㆍIn the event of an internal explosion within the ESS, the system enables emergency venting of explosion pressure and flames to the outside. |
||